Schneider Electric TWDALM3LT
Product information
$552.75 USD
Condition: newShipping calculated at checkout ( Shipping Policy · 30-Day Returns )
SKU: TWDALM3LT
Alternate: TWDALM3LT
Brand
Schneider Electric
Part No.
TWDALM3LT
Warranty
12 months
Lead time
3-7 days
In Stock— Ready to ship
Worldwide shipping available
Product Description
Schneider Electric TWDALM3LT
Product overview
The Schneider Electric TWDALM3LT is an automation spare part for Schneider Electric industrial automation equipment. Vcocnc supplies it for maintenance, breakdown repair and retrofit projects where the original part number has to be matched exactly.
Technical data
- Acquisition period: 500 ms + 1 controller cycle time
- Analogue input number: 2
- Analogue input resolution: 12 bits
- Analogue input type: Temperature probe temperature probe: Pt 100 3 wires differential Thermocouple -200...+760 °C thermocouple J differential Thermocouple -270...+1370 °C thermocouple K differential Thermocouple -270...+400 °C thermocouple T differential
- Analogue output number: 1
- Analogue output resolution: 12 bits
- Analogue output type: Current: 4...20 mA Voltage: 0...10 V
- Characteristic: Value(s)
- Common mode rejection: - 50 dB
- Conversion time: 20 ms + 1 controller cycle time
- Cross talk: <= 2 LSB
- Current consumption: 50 mA at 5 V DC 60 mA at 24 V DC
- I/O connection: Removable screw terminal block
- Input impedance: <= 250 Ohm thermocouple <= 5 Ohm temperature probe
- Input level: Low level
- Insulation between channel and internal logic: Photocoupler
- LSB value: 0.1 °C, analogue input type: thermocouple, thermocouple T 0.15 °K, analogue input type: temperature probe 0.3 °C, analogue input type: thermocouple, thermocouple J 0.325 °C, analogue input type: thermocouple, thermocouple K 2.5 mV voltage 4.8 µA current
- Load impedance ohmic: <= 300 Ohm current >= 2000 Ohm voltage
- Load type: Resistive
- Marking: CE
- Measurement error: +/- 0.2 % of full scale 0...10 V 0...10 V at 25 °C +/- 0.2 % of full scale 4...20 mA 4...20 mA at 25 °C +/- 0.2 % of full scale Pt at 25 °C 0.2 % +/- 4 °C of full scale thermocouple J at 25 °C 0.2 % +/- 4 °C of full scale thermocouple K at 25 °C 0.2 % +/- 4 °C of full scale thermocouple T at 25 °C
- Non-linearity: +/- 0.2 %FS, analogue input type: temperature probe +/- 0.2 %FS, analogue input type: thermocouple +/- 0.2 %FS, analogue output type: current +/- 0.2 %FS, analogue output type: voltage
- Output error: +/- 1 %FS
- Output ripple: <= 1 LSB
- Product or component type: Analogue I/O module
- Product weight: 0.085 kg
- Range of product: Twido
- Repeat accuracy: +/-0.5 %FS
- Sampling duration: 50 ms
- Sampling repetition time: 50 ms
- Stabilisation time: 20 ms
- Supply: External supply
- Supply voltage limits: 20.4â¦28.8 V
- Temperature coefficient: +/-0.006 %FS/°C, analogue input type: temperature probe +/-0.006 %FS/°C, analogue input type: thermocouple +/-0.015 %FS/°C, analogue output type: current +/-0.015 %FS/°C, analogue output type: voltage
- Total error: +/-1 %FS, analogue input type: temperature probe +/-1 %FS, analogue input type: thermocouple +/-1 %FS, analogue output type: current +/-1 %FS, analogue output type: voltage
- Type of cable: Shielded twisted pair
- [Us] rated supply voltage: 24 V DC
Condition and supply
- New surplus, never used
- In stock, lead time 3-7 days
- 12 months warranty
- Worldwide shipping with tracking
Before you order
Compare the full part number TWDALM3LT with the label on your original unit, including any suffix or revision code. Contact Vcocnc if you need help confirming compatibility.
Technical Specifications
- SKU
- TWDALM3LT
- Brand
- Schneider Electric
- Part Number
- TWDALM3LT
- Category
- Schneider Electric Other Parts
- Condition
- new
- Warranty
- 12 months
- Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair. Warranty policy
- Country of Origin
- China
- Supply
- External supply
- Marking
- CE
- LSB value
- 0.1 °C, analogue input type: thermocouple, thermocouple T 0.15 °K, analogue input type: temperature probe 0.3 °C, analogue input type: thermocouple, thermocouple J 0.325 °C, analogue input type: thermocouple, thermocouple K 2.5 mV voltage 4.8 µA current
- Load type
- Resistive
- Packaging
- New surplus, never used
- Cross talk
- <= 2 LSB
- Input level
- Low level
- Total error
- +/-1 %FS, analogue input type: temperature probe +/-1 %FS, analogue input type: thermocouple +/-1 %FS, analogue output type: current +/-1 %FS, analogue output type: voltage
- Output error
- +/- 1 %FS
- Non-linearity
- +/- 0.2 %FS, analogue input type: temperature probe +/- 0.2 %FS, analogue input type: thermocouple +/- 0.2 %FS, analogue output type: current +/- 0.2 %FS, analogue output type: voltage
- Output ripple
- <= 1 LSB
- Type of cable
- Shielded twisted pair
- Characteristic
- Value(s)
- I/O connection
- Removable screw terminal block
- Product weight
- 0.085 kg
- Conversion time
- 20 ms + 1 controller cycle time
- Input impedance
- <= 250 Ohm thermocouple <= 5 Ohm temperature probe
- Repeat accuracy
- +/-0.5 %FS
- Range of product
- Twido
- Measurement error
- +/- 0.2 % of full scale 0...10 V 0...10 V at 25 °C +/- 0.2 % of full scale 4...20 mA 4...20 mA at 25 °C +/- 0.2 % of full scale Pt at 25 °C 0.2 % +/- 4 °C of full scale thermocouple J at 25 °C 0.2 % +/- 4 °C of full scale thermocouple K at 25 °C 0.2 % +/- 4 °C of full scale thermocouple T at 25 °C
- Sampling duration
- 50 ms
- Acquisition period
- 500 ms + 1 controller cycle time
- Stabilisation time
- 20 ms
- Analogue input type
- Temperature probe temperature probe: Pt 100 3 wires differential Thermocouple -200...+760 °C thermocouple J differential Thermocouple -270...+1370 °C thermocouple K differential Thermocouple -270...+400 °C thermocouple T differential
- Current consumption
- 50 mA at 5 V DC 60 mA at 24 V DC
- Analogue output type
- Current: 4...20 mA Voltage: 0...10 V
- Load impedance ohmic
- <= 300 Ohm current >= 2000 Ohm voltage
- Analogue input number
- 2
- Common mode rejection
- - 50 dB
- Supply voltage limits
- 20.4â¦28.8 V
- Analogue output number
- 1
- Temperature coefficient
- +/-0.006 %FS/°C, analogue input type: temperature probe +/-0.006 %FS/°C, analogue input type: thermocouple +/-0.015 %FS/°C, analogue output type: current +/-0.015 %FS/°C, analogue output type: voltage
- Sampling repetition time
- 50 ms
- Analogue input resolution
- 12 bits
- Product or component type
- Analogue I/O module
- [Us] rated supply voltage
- 24 V DC
- Analogue output resolution
- 12 bits
- Insulation between channel and internal logic
- Photocoupler
Compatibility Information
Match TWDALM3LT against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.
Installation Guide
Isolate power and follow the Schneider Electric documentation for the host system when replacing TWDALM3LT.
Maintenance Tips
Store TWDALM3LT dry and dust-free in its packaging until installation.
Frequently Asked Questions
Yes. TWDALM3LT is in stock and ships within 1-2 business days, with a tracking number for every shipment.
TWDALM3LT is supplied with a warranty of 12 months. Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair.
Match TWDALM3LT against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.
Customer Reviews
No reviews yet. Verified buyers can share their experience with this part.
Purchased this part? Sign in to leave a review. Only verified buyers can review.
Sign in to reviewReviews are checked by our team before they appear.
Explore More Options
Related Products
Schneider Electric ZR2FA2
SKU: ZR2FA2
Schneider Electric ZMLPA2P0SH
SKU: ZMLPA2P0SH
Schneider Electric ZMLPA2N0SH
SKU: ZMLPA2N0SH
Schneider Electric ZMLPA1P2SW
SKU: ZMLPA1P2SW