+86 13348028050
RM35LM33MW Schneider Electric RM35LM33MW - Front View | Vcocnc FANUC Parts

Schneider Electric RM35LM33MW

Product information

$150.84 USD

Condition: new

Shipping calculated at checkout ( Shipping Policy · 30-Day Returns )

SKU: RM35LM33MW

Alternate: RM35LM33MW

Brand
Schneider Electric
Part No.
RM35LM33MW
Warranty
12 months
Lead time
3-7 days
In Stock— Ready to ship
Worldwide shipping available
12 months Warranty
Worldwide Shipping
Quality Tested

Product Description

Schneider Electric RM35LM33MW Product overview The Schneider Electric RM35LM33MW is an automation spare part for Schneider Electric industrial automation equipment. Vcocnc supplies it for maintenance, breakdown repair and retrofit projects where the original part number has to be matched exactly. Technical data - Cable capacitance: 1 nF HS (High Sensitivity) probe cable 2.2 nF St (Standard Sensitivity) probe cable 4.7 nF LS (Low Sensitivity) - Characteristic: Value(s) - Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end - Contacts type and composition: 2 C/O - Electrical durability: 100000 cycles - Housing material: Self-extinguishing plastic - Insulation resistance: > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 > 1 MOhm 500 V DC between supply and measurement IEC 60664-1 - Local signalling: LED (yellow) for relay ON LED (green) for power ON LED (yellow) for timer ON - Marking: CE : 73/23/EEC CE : EMC 89/336/EEC - Maximum supply current for sensors: 1 mA - Maximum switching current: 5 A AC/DC - Maximum switching voltage: 250 V AC/DC - Measurement accuracy: +/- 10 % of the full scale value +/- 20 % for the HS range - Measurement error: 0.5 %/°C with temperature variation - Measurement range: 250 Ohm...1 MOhm - Minimum switching current: 10 mA 5 V DC - Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715 - Operating position: Any position without derating - Output contacts: 2 C/O - Overvoltage category: III conforming to IEC 60664-1 - Product or Component Type: Level control relay - Range of Product: Harmony Control Relays - Relay Type: Level control relay - Relay monitored parameters: Detection by resistive probes - Relay name: RM35L - Repeat accuracy: +/- 2 % time delay - Reset time: 1750 ms - Sensitivity adjustment: 5…100 % - Sensitivity scale: 0.25...5 kOhm LS (Low Sensitivity) 5...100 kOhm St (Standard Sensitivity) 50...1000 kOhm HS (High Sensitivity) - Supply voltage limits: 20.4…264 V AC/DC - Switching capacity in VA: 1250 VA - Tightening torque: 5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1 - Utilisation category: AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 - [Ui] rated insulation voltage: 250 V IEC 60664-1 - [Un] rated nominal voltage: 24...240 V AC/DC 50/60 Hz, non self-powered - delay at power up: 0.6 s - nominal output current: 5 A - operating voltage tolerance: - 15 % + 10 % Un - power consumption: 5 VA AC - time delay: Adjustable 0.1...5 s, +/- 10 % Tt- time delay upon fault Condition and supply - New surplus, factory sealed original packaging - In stock, lead time 3-7 days - 12 months warranty - Worldwide shipping with tracking Before you order Compare the full part number RM35LM33MW with the label on your original unit, including any suffix or revision code. Contact Vcocnc if you need help confirming compatibility.

Technical Specifications

SKU
RM35LM33MW
Brand
Schneider Electric
Part Number
RM35LM33MW
Category
Schneider Electric Other Parts
Condition
new
Warranty
12 months
Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair. Warranty policy
Country of Origin
China
Marking
CE : 73/23/EEC CE : EMC 89/336/EEC
Packaging
New surplus, factory sealed original packaging
Relay Type
Level control relay
Relay name
RM35L
Reset time
1750 ms
time delay
Adjustable 0.1...5 s, +/- 10 % Tt- time delay upon fault
Characteristic
Value(s)
Output contacts
2 C/O
Repeat accuracy
+/- 2 % time delay
Housing material
Self-extinguishing plastic
Local signalling
LED (yellow) for relay ON LED (green) for power ON LED (yellow) for timer ON
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Range of Product
Harmony Control Relays
Cable capacitance
1 nF HS (High Sensitivity) probe cable 2.2 nF St (Standard Sensitivity) probe cable 4.7 nF LS (Low Sensitivity)
Measurement error
0.5 %/°C with temperature variation
Measurement range
250 Ohm...1 MOhm
Sensitivity scale
0.25...5 kOhm LS (Low Sensitivity) 5...100 kOhm St (Standard Sensitivity) 50...1000 kOhm HS (High Sensitivity)
Tightening torque
5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1
delay at power up
0.6 s
power consumption
5 VA AC
Operating position
Any position without derating
Measurement accuracy
+/- 10 % of the full scale value +/- 20 % for the HS range
Overvoltage category
III conforming to IEC 60664-1
Utilisation category
AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1
Electrical durability
100000 cycles
Insulation resistance
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5 > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
Supply voltage limits
20.4…264 V AC/DC
Sensitivity adjustment
5…100 %
nominal output current
5 A
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
Switching capacity in VA
1250 VA
Maximum switching current
5 A AC/DC
Maximum switching voltage
250 V AC/DC
Minimum switching current
10 mA 5 V DC
Product or Component Type
Level control relay
Relay monitored parameters
Detection by resistive probes
[Un] rated nominal voltage
24...240 V AC/DC 50/60 Hz, non self-powered
operating voltage tolerance
- 15 % + 10 % Un
Contacts type and composition
2 C/O
[Ui] rated insulation voltage
250 V IEC 60664-1
Maximum supply current for sensors
1 mA

Compatibility Information

Match RM35LM33MW against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.

Installation Guide

Isolate power and follow the Schneider Electric documentation for the host system when replacing RM35LM33MW.

Maintenance Tips

Store RM35LM33MW dry and dust-free in its packaging until installation.

Frequently Asked Questions

Customer Reviews

No reviews yet. Verified buyers can share their experience with this part.

Purchased this part? Sign in to leave a review. Only verified buyers can review.

Sign in to review

Reviews are checked by our team before they appear.

Explore More Options