KEYENCE KV-TP40
Product information
$342.32 USD
Condition: newShipping calculated at checkout ( Shipping Policy · 30-Day Returns )
SKU: KV-TP40
Alternate: KVTP40
Brand
KEYENCE
Part No.
KV-TP40
Warranty
12 months
Lead time
3-7 days
In Stock— Ready to ship
Worldwide shipping available
Product Description
KEYENCE KV-TP40
Product overview
The KEYENCE KV-TP40 is an automation spare part for KEYENCE industrial automation equipment. Vcocnc supplies it for maintenance, breakdown repair and retrofit projects where the original part number has to be matched exactly.
Technical data
- Cold junction correction precision: ±1°C ±1.8°F (during thermocouple input)
- Conversion speed: 50 ms/4 ch
- Indicated accuracy: ±0.2% of F.S. (at 25°C ±5°C 77°F ±9°F ), ±0.4% of F.S. (at 0 to 50°C 32 to 122°F )
- Input: Thermocoupler/Platinum temperature measuring resistor/Voltage and current
- Input range / Thermocoupler: K: -270.0 to 1372.0°C -454 to 2502°F J: -210.0 to 1200.0°C -346 to 2192°F T: -270.0 to 400.0°C -454 to 752°F E: -270.0 to 1000.0°C -454 to 1832°F N: -270.0 to 1300.0°C -454 to 2372°F R: -50.0 to 1768.0°C -58 to 3214°F S: -50.0 to 1768.0°C -58 to 3214°F B: 0.0 to 1820.0°C 32 to 3308°F WRe5-26: 0.0 to 2315.0°C 32 to 4199°F
- Input resistance: Voltage: 1 MΩ, Current: 250 Ω
- Insulation mode: Between an input terminal and CPU: Photocoupler and transformer insulation, Between channels: Photocoupler and transformer insulation
- Internal current consumption: 90 mA or less
- Number of temperature input points: 4 ch
- Others: External cold junction correction, wire-breaking detection function, scaling function, average processing function (time average, average of the number of times, moving average, primary delay filter), special data offset function, alarm function, rate of change calculation, rate of change alarm function
- Platinum temperature measuring resistor: Pt100: -200.0 to 850.0°C -328 to 1562°F JPt100: -200.0 to 600.0°C -328 to 1112°F
- Type: Temperature/Analog multi-input unit
- Voltage and current: Voltage: -10 to +10 V (0.5 mV 1/40000) 0 V to 10 V (0.5 mV 1/20000) -5 V to +5 V (0.5 mV 1/20000) 0 V to 5 V (0.5 mV 1/10000) 1 V to 5 V (0.5 mV 1/8000) -100 mV to +100 mV (5 μV 1/40000) 0 mV to 100 mV (5 μV 1/20000) Current: 0 mA to 20 mA (2 μA 1/10000) 4 mA to 20 mA (2 μA 1/8000)
- Weight: Approx. 190 g
Condition and supply
- New surplus, factory sealed original packaging
- In stock, lead time 3-7 days
- 12 months warranty
- Worldwide shipping with tracking
Before you order
Compare the full part number KV-TP40 with the label on your original unit, including any suffix or revision code. Contact Vcocnc if you need help confirming compatibility.
Technical Specifications
- SKU
- KV-TP40
- Brand
- KEYENCE
- Part Number
- KV-TP40
- Category
- KEYENCE Other Parts
- Condition
- new
- Warranty
- 12 months
- Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair. Warranty policy
- Country of Origin
- China
- Type
- Temperature/Analog multi-input unit
- Input
- Thermocoupler/Platinum temperature measuring resistor/Voltage and current
- Others
- External cold junction correction, wire-breaking detection function, scaling function, average processing function (time average, average of the number of times, moving average, primary delay filter), special data offset function, alarm function, rate of change calculation, rate of change alarm function
- Weight
- Approx. 190 g
- Packaging
- New surplus, factory sealed original packaging
- Insulation mode
- Between an input terminal and CPU: Photocoupler and transformer insulation, Between channels: Photocoupler and transformer insulation
- Conversion speed
- 50 ms/4 ch
- Input resistance
- Voltage: 1 MΩ, Current: 250 Ω
- Indicated accuracy
- ±0.2% of F.S. (at 25°C ±5°C 77°F ±9°F ), ±0.4% of F.S. (at 0 to 50°C 32 to 122°F )
- Voltage and current
- Voltage: -10 to +10 V (0.5 mV 1/40000) 0 V to 10 V (0.5 mV 1/20000) -5 V to +5 V (0.5 mV 1/20000) 0 V to 5 V (0.5 mV 1/10000) 1 V to 5 V (0.5 mV 1/8000) -100 mV to +100 mV (5 μV 1/40000) 0 mV to 100 mV (5 μV 1/20000) Current: 0 mA to 20 mA (2 μA 1/10000) 4 mA to 20 mA (2 μA 1/8000)
- Input range / Thermocoupler
- K: -270.0 to 1372.0°C -454 to 2502°F J: -210.0 to 1200.0°C -346 to 2192°F T: -270.0 to 400.0°C -454 to 752°F E: -270.0 to 1000.0°C -454 to 1832°F N: -270.0 to 1300.0°C -454 to 2372°F R: -50.0 to 1768.0°C -58 to 3214°F S: -50.0 to 1768.0°C -58 to 3214°F B: 0.0 to 1820.0°C 32 to 3308°F WRe5-26: 0.0 to 2315.0°C 32 to 4199°F
- Internal current consumption
- 90 mA or less
- Cold junction correction precision
- ±1°C ±1.8°F (during thermocouple input)
- Number of temperature input points
- 4 ch
- Platinum temperature measuring resistor
- Pt100: -200.0 to 850.0°C -328 to 1562°F JPt100: -200.0 to 600.0°C -328 to 1112°F
Compatibility Information
Match KV-TP40 against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.
Installation Guide
Isolate power and follow the KEYENCE documentation for the host system when replacing KV-TP40.
Maintenance Tips
Store KV-TP40 dry and dust-free in its packaging until installation.
Frequently Asked Questions
Yes. KV-TP40 is in stock and ships within 1-2 business days, with a tracking number for every shipment.
KV-TP40 is supplied with a warranty of 12 months. Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair.
Match KV-TP40 against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.
Customer Reviews
No reviews yet. Verified buyers can share their experience with this part.
Purchased this part? Sign in to leave a review. Only verified buyers can review.
Sign in to reviewReviews are checked by our team before they appear.
Explore More Options
Related Products
KEYENCE EH-108
SKU: EH-108
KEYENCE EH-110
SKU: EH-110
KEYENCE EH-110S
SKU: EH-110S
KEYENCE EH-114
SKU: EH-114