+86 13348028050
GV3P321 Schneider Electric GV3P321 - Front View | Vcocnc FANUC Parts

Schneider Electric GV3P321

Product information

SKU: GV3P321

Alternate: GV3P321

Brand
Schneider Electric
Part No.
GV3P321
Warranty
12 months
Lead time
3-7 days
In Stock— Ready to ship
Worldwide shipping available
12 months Warranty
Worldwide Shipping
Quality Tested

Product Description

Schneider Electric GV3P321 Product overview The Schneider Electric GV3P321 is an automation spare part for Schneider Electric industrial automation equipment. Vcocnc supplies it for maintenance, breakdown repair and retrofit projects where the original part number has to be matched exactly. Technical data - Breaking capacity: 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 - Characteristic: Value(s) - Colour: Dark grey - Depth: 136 mm - Device application: Motor protection - Device short name: GV3P - Electrical durability: 50000 cycles for AC-3 at 415 V In - Fixing mode: 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) - Height: 132 mm - Magnetic tripping current: 448 A - Mechanical durability: 50000 cycles - Motor power kW: 15 kW at 400/415 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 22 kW at 690 V AC 50/60 Hz - Mounting position: Horizontal Vertical - Network frequency: 50/60 Hz conforming to IEC 60947-2 - Network type: AC - Phase failure sensitivity: Yes conforming to IEC 60947-4-1 - Poles description: 3P - Power dissipation per pole: 8 W - Product or component type: Motor circuit breaker - Product weight: 0.96 kg - Range: TeSys Deca - Rated duty: Uninterrupted conforming to IEC 60947-4-1 - Suitability for isolation: Yes conforming to IEC 60947-1 - Thermal protection adjustment range: 23…32 A conforming to IEC 60947-2 - Tightening torque: 5 N.m - on screw clamp terminal - Trip unit technology: Thermal-magnetic - Utilisation category: Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 - Width: 55 mm - [Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 - [In] rated current: 32 A - [Ith] conventional free air thermal current: 32 A conforming to IEC 60947-2 - [Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2 - [Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2 - [Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2 - control type: Rotary handle - product name: TeSys GV3 Condition and supply - Price on request: send an inquiry with the quantity you need - 12 months warranty - Worldwide shipping with tracking Before you order Compare the full part number GV3P321 with the label on your original unit, including any suffix or revision code. Contact Vcocnc if you need help confirming compatibility.

Technical Specifications

SKU
GV3P321
Brand
Schneider Electric
Part Number
GV3P321
Category
Schneider Electric Other Parts
Condition
new
Warranty
12 months
Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair. Warranty policy
Country of Origin
China
Depth
136 mm
Range
TeSys Deca
Width
55 mm
Colour
Dark grey
Height
132 mm
Rated duty
Uninterrupted conforming to IEC 60947-4-1
Fixing mode
35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws)
Network type
AC
control type
Rotary handle
product name
TeSys GV3
Characteristic
Value(s)
Motor power kW
15 kW at 400/415 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 22 kW at 690 V AC 50/60 Hz
Product weight
0.96 kg
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Device short name
GV3P
Mounting position
Horizontal Vertical
Network frequency
50/60 Hz conforming to IEC 60947-2
Poles description
3P
Tightening torque
5 N.m - on screw clamp terminal
Device application
Motor protection
[In] rated current
32 A
Trip unit technology
Thermal-magnetic
Utilisation category
Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
Electrical durability
50000 cycles for AC-3 at 415 V In
Mechanical durability
50000 cycles
Magnetic tripping current
448 A
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Product or component type
Motor circuit breaker
Suitability for isolation
Yes conforming to IEC 60947-1
Power dissipation per pole
8 W
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Thermal protection adjustment range
23…32 A conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
[Ith] conventional free air thermal current
32 A conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Compatibility Information

Match GV3P321 against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.

Installation Guide

Isolate power and follow the Schneider Electric documentation for the host system when replacing GV3P321.

Maintenance Tips

Store GV3P321 dry and dust-free in its packaging until installation.

Frequently Asked Questions

Customer Reviews

No reviews yet. Verified buyers can share their experience with this part.

Purchased this part? Sign in to leave a review. Only verified buyers can review.

Sign in to review

Reviews are checked by our team before they appear.

Explore More Options