+86 13348028050
ATS48D62Y Schneider Electric ATS48D62Y - Front View | Vcocnc FANUC Parts

Schneider Electric ATS48D62Y

Product information

$3,424.20 USD

Condition: new

Shipping calculated at checkout ( Shipping Policy · 30-Day Returns )

SKU: ATS48D62Y

Alternate: ATS48D62Y

Brand
Schneider Electric
Part No.
ATS48D62Y
Warranty
12 months
Lead time
3-7 days
In Stock— Ready to ship
Worldwide shipping available
12 months Warranty
Worldwide Shipping
Quality Tested

Product Description

Schneider Electric ATS48D62Y Product overview The Schneider Electric ATS48D62Y is an automation spare part for Schneider Electric industrial automation equipment. Vcocnc supplies it for maintenance, breakdown repair and retrofit projects where the original part number has to be matched exactly. Technical data - Analogue output type: Current output AO 0-20 mA or 4-20 mA 500 Ohm - Characteristic: Value(s) - Communication Port Protocol: Modbus - Communication data link: Serial - Connector Type: 1 RJ45 - Depth: 9.3 in (235 mm) - Device connection: In the motor supply line - Device short name: ATS48 - Discrete input logic: Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA - Discrete input number: 5 - Discrete input type: PTC, 750 Ohm 77 °F (25 °C) Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm - Discrete output number: 2 - Discrete output type: LO1) logic output 0 V common configurable LO2) logic output 0 V common configurable R1) relay outputs fault relay NO R2) relay outputs end of starting relay NO R3) relay outputs motor powered NO - Function Available: External bypass (optional) - Height: 11.4 in (290 mm) - Marking: CE - Maximum Horse Power Rating: 15 hp 208 V for standard applications 15 hp 230 V for severe applications 20 hp 230 V for standard applications 30 hp 460 V for severe applications 40 hp 460 V for standard applications 40 hp 575 V for severe applications 50 hp 575 V for standard applications - Minimum switching current: 10 mA 6 V DC relay outputs - Motor power kW: 11 kW 230 V for severe applications 15 kW 230 V for standard applications 22 kW 400 V for severe applications 22 kW 440 V for severe applications 30 kW 400 V for standard applications 30 kW 440 V for standard applications 30 kW 500 V for severe applications 30 kW 525 V for severe applications 37 kW 500 V for standard applications 37 kW 525 V for standard applications 37 kW 660 V for severe applications 37 kW 690 V for severe applications 45 kW 660 V for standard applications 45 kW 690 V for standard applications - Operating position: Vertical +/- 10 degree - Physical interface: RS485 multidrop - Product Certifications: NOM 117 GOST TCF UL DNV CCC SEPRO C-tick CSA - Product Specific Application: Heavy duty industry and pumps - Product Weight: 18.3 lb(US) (8.3 kg) - Product destination: Asynchronous motors - Product or Component Type: Soft starter - Protection type: Phase failure line Thermal protection motor Thermal protection starter - Range of Product: Altistart 48 - Standards: IEC 60947-4-2 - Transmission Rate: 4800, 9600 or 19200 bps - Ue power supply voltage: 208...690 V - 15...10 % - Utilisation category: AC-53A - Width: 7.5 in (190 mm) - power supply frequency: 50...60 Hz - 5...5 % Condition and supply - New surplus, never used - In stock, lead time 3-7 days - 12 months warranty - Worldwide shipping with tracking Before you order Compare the full part number ATS48D62Y with the label on your original unit, including any suffix or revision code. Contact Vcocnc if you need help confirming compatibility.

Technical Specifications

SKU
ATS48D62Y
Brand
Schneider Electric
Part Number
ATS48D62Y
Category
Schneider Electric Other Parts
Condition
new
Warranty
12 months
Covers manufacturing defects and functional failures under normal use; excludes damage from improper installation, misuse or unauthorized repair. Warranty policy
Country of Origin
China
Depth
9.3 in (235 mm)
Width
7.5 in (190 mm)
Height
11.4 in (290 mm)
Marking
CE
Packaging
New surplus, never used
Standards
IEC 60947-4-2
Characteristic
Value(s)
Connector Type
1 RJ45
Motor power kW
11 kW 230 V for severe applications 15 kW 230 V for standard applications 22 kW 400 V for severe applications 22 kW 440 V for severe applications 30 kW 400 V for standard applications 30 kW 440 V for standard applications 30 kW 500 V for severe applications 30 kW 525 V for severe applications 37 kW 500 V for standard applications 37 kW 525 V for standard applications 37 kW 660 V for severe applications 37 kW 690 V for severe applications 45 kW 660 V for standard applications 45 kW 690 V for standard applications
Product Weight
18.3 lb(US) (8.3 kg)
Protection type
Phase failure line Thermal protection motor Thermal protection starter
Range of Product
Altistart 48
Device connection
In the motor supply line
Device short name
ATS48
Transmission Rate
4800, 9600 or 19200 bps
Function Available
External bypass (optional)
Operating position
Vertical +/- 10 degree
Physical interface
RS485 multidrop
Discrete input type
PTC, 750 Ohm 77 °F (25 °C) Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Product destination
Asynchronous motors
Analogue output type
Current output AO 0-20 mA or 4-20 mA 500 Ohm
Discrete input logic
Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
Discrete output type
LO1) logic output 0 V common configurable LO2) logic output 0 V common configurable R1) relay outputs fault relay NO R2) relay outputs end of starting relay NO R3) relay outputs motor powered NO
Utilisation category
AC-53A
Discrete input number
5
Discrete output number
2
Product Certifications
NOM 117 GOST TCF UL DNV CCC SEPRO C-tick CSA
power supply frequency
50...60 Hz - 5...5 %
Communication data link
Serial
Ue power supply voltage
208...690 V - 15...10 %
Minimum switching current
10 mA 6 V DC relay outputs
Product or Component Type
Soft starter
Maximum Horse Power Rating
15 hp 208 V for standard applications 15 hp 230 V for severe applications 20 hp 230 V for standard applications 30 hp 460 V for severe applications 40 hp 460 V for standard applications 40 hp 575 V for severe applications 50 hp 575 V for standard applications
Communication Port Protocol
Modbus
Product Specific Application
Heavy duty industry and pumps

Compatibility Information

Match ATS48D62Y against the original part label and the machine or panel configuration before ordering; suffixes and revision codes matter.

Installation Guide

Isolate power and follow the Schneider Electric documentation for the host system when replacing ATS48D62Y.

Maintenance Tips

Store ATS48D62Y dry and dust-free in its packaging until installation.

Frequently Asked Questions

Customer Reviews

No reviews yet. Verified buyers can share their experience with this part.

Purchased this part? Sign in to leave a review. Only verified buyers can review.

Sign in to review

Reviews are checked by our team before they appear.

Explore More Options